A water treatment system service and maintenance plan, such as that of Commercial RO Plant is an affordable, interference-free way to guarantee that the system is performing as it should. Netsol Water provides upkeep and servicing to guarantee that water treatment systems are operating at their best.
Let us see how commercial RO plants are maintained during downtime.
How is the Commercial RO Plant maintained?
Options for preventive maintenance and service include:
· Pretreatment system maintenance, such as for water softeners.
· Systems for reverse osmosis involve changing membranes, cleaning on-site (CIP) with chemicals, and routine maintenance.
· Post treatment involves routine maintenance and ultraviolet (UV) sterilizers.
· Ion exchange facility maintenance includes loading and unloading resins as well as routine maintenance and plant servicing.
· Ozone system maintenance as usual.
How is the Commercial RO Plant maintained during downtime?
Reverse osmosis systems are typically unable to function continuously for an extended amount of time, when used to treat water for a variety of reasons.
When the reverse osmosis plant is out of commission for an extended period of time, several maintenance procedures are developed based on how long the plant has been out of commission.
1: Feed the commercial reverse osmosis membrane plant with membrane system product water (low pressure, high flow rate).
2: After flushing, keep the relevant piping and valves closed until the conductivity of the influent water and the concentrated water are consistent.
3: In order to avoid the formation of germs, it is necessary to flush once every 24 hours using the procedure described above. If the surrounding temperature is higher than 27°C, the flushing frequency should be reduced to once every 12 hours.
Perform these if the prolonged inactivity is greater than 48 hours:
1: Perform a cleaning and sterilisation procedure with chemicals.
2: Prepare protection fluid (1.0% sodium bisulfite) for cleansing and filling the Commercial RO Plant, and shut all valves to keep air from getting in and causing the protection fluid to fail.
3: Every week, check the protective solution's pH level; if it falls below 3, replace the protective solution right away.
4: If the outside temperature is above 27 degrees Celsius, the time should be lowered to 15 days. Otherwise, flush and refill the protective fluid as described above every 30 days.
5: During the closure, the storage temperature of the reverse osmosis plant should be maintained at (5-45)°C.
6: When the Commercial RO plant is used again, flush the reverse osmosis system with high flow rates and low pressures of produced water, for at least an hour before flushing with high pressure for five to ten minutes, to ensure the produced water is suitable;
Conclusion
Keep in mind that before flushing, the membrane system's generated water outlet valve needs to be fully opened, to prevent back pressure and produced water from entering the tank.
If you want to get high-quality Commercial RO plants, call Netsol Water right away!
Netsol Water is a corporation based in Greater Noida, India. Our skilled technicians can perform services, maintenance, and replacements on-site, and can offer all the necessary technical assistance to produce the finest outcomes.
We have been offering India's top Commercial RO Plants for many years. Thus, we are delighted to offer you field services as well as assistance with your choice of treatment products, in addition to providing comprehensive system design and engineering. To find out more, get in touch with us at +91 9650608473 or enquiry@netsolwater.com